﻿If a group or single device is to be switched on by starting a brightness sequence, the sequence starts at a configurable start value.

*Preset*: A fixed start value is preset as the start brightness value. Make sure the configured brightness value is not below the set minimum brightness or above the maximum brightness! Otherwise, the gateway will limit the start value to minimum or maximum brightness.

*Memory value (value before switching-off last time)*: When starting, the brightness value that was active and stored internally before the last switch-off is set. This memory value is stored in a non-volatile manner in the gateway so that the value is retained after the bus or mains voltage returns. After programming with the ETS, the value is predefined to maximum brightness.

*Value as before last stop*: The brightness sequence starts at the brightness value at which a stop was last executed during the previous brightness sequence.